EasyManua.ls Logo

Invertek Drives Optidrive E3 ODE-3 Series - Generic device configuration with Enabled Routing (Other PLC type); Configuration example for Standard Telegram (4 Words In; 4 Words Out); Device configuration for Extended Status Information (Advanced Telegram with 4 Words In;16 Words Out); Advanced connection methods

Invertek Drives Optidrive E3 ODE-3 Series
62 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
40 | Fieldbus Guide | Version 1.02 www.invertekdrives.com
8
Ethernet/IP Communication
8.6.4.2. Generic device confi guration with Enabled Routing (Other PLC type)
Communication as a Generic deice is also possible with PLC’s that support routing through a CIP Modbus Translator.
For detailed information please refer to the programming documentation of the PLC.
A typical example confi guration is shown below.
Network confi guration
Add a Generic Device to the EtherNet/IP network, assign the
device name and IP address
Message confi guration
Please add the I/O Message and confi gure it as below
NOTE
Slot number must be set to 1 and be equal to the drive local
network address (Parameter P-36).
Device confi guration for Standard Telegram (4 Words In/ 4 Words Out)
Target to Originator: Originator to Target:
Device confi guration for Extended Status Information (Advanced Telegram with 4 Words In/ 16 Words Out)
Target to Originator: Originator to Target:
8.7. Advanced connection methods
Communication to the drive may also be possible using one of the two methods shown below. This allows process data to be
cyclically exchanged between the Ethernet/IP master and a connected Optidrive.
Both of the following methods are pre-defi ned within the available EDS fi les.
8.7.1. Method 1: Class 1 connection to Drive Assembly object
Drive control can be achieved via Class1 connections to the Assembly Object (0x04).
The controller must implement the forward open request (routing) to the OPT-2-ETHEG-IN Port 3, address 1.
For Drive specifi c allocation refer to Drive Manual and/or Ethernet/IP EDS fi le.
For Drive specifi c read/write limitations refer to Drive Manual and/or Ethernet/IP EDS fi le.
NOTE
Slot number must be set to 1 and be equal to the drive local
network address (Parameter P-36).
Device confi guration for Standard Telegram (4 Words In/ 4 Words Out)
Target to Originator:
Originator to Target:
Device confi guration for Extended Status Information (Advanced Telegram with 4 Words In/ 16 Words Out)
Target to Originator:
Originator to Target:

Table of Contents