EasyManua.ls Logo

Invertek Drives Optidrive E3 ODE-3 Series - Explicit Messaging; Parameter data transfer - configuration example based on Allen Bradley Studio 5000 Logix Designer; Read Parameter Value

Invertek Drives Optidrive E3 ODE-3 Series
62 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
42 | Fieldbus Guide | Version 1.02 www.invertekdrives.com
8
Ethernet/IP Communication
8.8.2. Explicit Messaging
Explicit messaging can be used to read or write a parameter setting.
All drives parameter variables have the data type INT (16 bit, 2-byte objects). The device parameters and the PLC program variables
must have the same data lengths.
Accessing drive parameters
Explicit messaging must be confi gured using the settings shown below.
Explicit Message Read Request Confi guration
Read Message Type Single Parameter Read Multiple Parameters Read
Service ID 14 (0x0E) 78 (0x4E)
Class ID 15 (0x0F) 68 (0x44)
Attribute ID 1 (0x01) -
Instance ID Modbus Register assigned to the Parameter Number
Data Type INT (16-bit)
Data Size 16-bit 16-bit x Number of Requested Elements
Explicit Message Write Request Confi guration
Read Message Type Single Parameter Write Multiple Parameters Write
Service ID 16 (0x10) Not supported
Class ID 15 (0x0F) Not supported
Attribute ID 1 (0x01) Not supported
Instance ID Modbus Register assigned to the Parameter Number
Data Type INT (16-bit)
Data Size 16-bit -
8.8.2.1. Parameter data transfer - confi guration example based on Allen Bradley Studio 5000 Logix Designer
8.8.2.1.1. Read Parameter Value
Please add the MSG function to the program.
Massage Confi guration Parameter Read
Confi guration Tab: Communication Tab:
Class ID
15 (0x0F)
68 (0x44)
Attribute ID
1 (0x01)
-
Instance ID
Modbus Register assigned to the Parameter Number
Data Type
INT (16-bit)
Data Size
16-bit
16-bit x Number of Requested Elements
Explicit Message Write Request Confi guration
Read Message Type
Single Parameter Write
Multiple Parameters Write
Service ID
16 (0x10)
Not supported
Class ID
15 (0x0F)
Not supported
Attribute ID
1 (0x01)
Not supported
Instance ID
Modbus Register assigned to the Parameter Number
Data Type
INT (16-bit)
Data Size
16-bit
-
8.8.2.1. Parameter data transfer - confi guration example based on Allen Bradley Studio 5000 Logix Designer
8.8.2.1.1. Read Parameter Value
Please add the MSG function to the program.
Massage Confi guration Parameter Read
Confi guration Tab:
Communication Tab:

Table of Contents

Related product manuals