44 | Fieldbus Guide | Version 1.02 www.invertekdrives.com
8
Ethernet/IP Communication
Network Status (NS) Indicator
State Ethernet/IP
Steady Off Not powered
No IP address
Steady Green Online
One or more connections active or message received
Flashing Green
Online
No connections active or no messages received
Flashing Red Connection timeout
Steady Red Duplicate IP
Flashing Green and Red Self-test
Module Status (MS) Indicator
State Indication
Steady Off No power
Steady Green Operating in normal condition
Flashing Green Drive not configured
Flashing Red Minor fault - Recoverable fault
Steady Red Major fault - Unrecoverable fault
Flashing Green / Red Self-test
COMM
State Indication
Steady Off Modbus protocol TX/RX inactive
Steady/flashing Yellow Modbus protocol TX/RX active
ERROR
State Indication
Steady Off Modbus protocol TX/RX Status OK
Steady Red Non-recoverable internal fault – Modbus communications circuit fault
Flashing Red Recoverable Communication fault or configuration error
Link Activity LEDs (P1/P2)
State State Indication
P1 Speed Steady Yellow 100Mbps link active
Steady Off 10Mbps or No link
P1 Link Activity Steady Green Valid Link
Steady Off No Link
Flash TX/RX
P2 Speed Steady Yellow 100Mbps link active
Steady Off 10Mbps or No link
P2 Link Activity Steady Green Valid Link
Steady Off No Link
Flash TX/RX
Operating in normal condition
Minor fault - Recoverable fault
Major fault - Unrecoverable fault
Flashing Green / Red Self-test
Flashing Green / Red Self-test
Modbus protocol TX/RX inactive
Steady/flashing Yellow Modbus protocol TX/RX active
Steady/flashing Yellow Modbus protocol TX/RX active
Modbus protocol TX/RX Status OK
Non-recoverable internal fault – Modbus communications circuit fault
Recoverable Communication fault or configuration error
Link Activity LEDs (P1/P2)