DA180 series basic AC servo drive Function codes
-79-
Internal enabling
command
This parameter is used to control the working status of the servo drive.
The mapping between the settings of this parameter and external terminal enabling commands
are as follows:
External terminal command
0 (The internal optical coupler
corresponding to the input is not
conducted.)
1 (The internal optical coupler
corresponding to the input is conducted.)
0 (The internal optical coupler
corresponding to the input is not
conducted.)
1 (The internal optical coupler
corresponding to the input is conducted.)
Note:
If P0.04 is set to 1, but the external terminal command status is changed from 1 to 0, the drive
is disabled, that is, P0.04 is changed to 0 automatically.
The method for setting this parameter on the LED panel is different from that for setting other
parameters. You can use only the SET key to switch between 0 and 1. The UP/DOWN key is
invalid on the screen for setting this parameter.
This parameter specifies the jogging speed. For details, see 5.2.5.2 "Jogging test". During the
jogging process, the ACC/DEC time parameters P0.54, P0.55, P0.56, P0.57 function, and the
motor accelerates, decelerates, starts, or stops based on the settings.