Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-103-
Detailed instruction of parameters
the inverter will output underload pre-alarm.
Setting range of P11.11: 0~P11.09
Setting range of P11.12: 0.1~3600.0s
Underload
pre-alarm
detection
time
Output
terminal
action
during fault
Select the action of fault output terminals on
undervoltage and fault reset.
0x00~0x11
LED ones:
0: Action under fault undervoltage
1: No action under fault undervoltage
LED tens:
0: Action during the automatic reset
1: No action during the automatic reset
Speed
deviation
detection
0.0~50.0%
Set the speed deviation detection time.
Speed
deviation
detection
time
This parameter is used to set the speed deviation
detection time.
Setting range of P11.15: 0.0~10.0s
Automatic
frequency
decreasing
at voltage
0: Invalid
1: Valid; ensure rated output torque when voltage
drop