Goodrive300-19 series open loop vector inverter special for hosit Basic operation instruction
-130-
5: Customized V/F (V/F separation)
P04.01
Torque boost
of motor 1
0.0%: (automatic) 0.1%~10.0%
0.0%
P04.02
Torque boost
close of motor 1
0.0%~50.0% (rated frequency of motor 1)
20.0%
P04.03
V/F
frequency 1 of
motor 1
0.00Hz~P04.05
0.00Hz
P04.04
V/F
voltage 1 of
motor 1
0.0%~110.0%
00.0%
P04.05
V/F
frequency 2 of
motor 1
P04.03~P04.07
00.00Hz
P04.06
V/F
voltage 2 of
motor 1
0.0%~110.0%
00.0%
P04.07
V/F
frequency 3 of
motor 1
P04.05~P02.02 or P04.05~P02.16
00.00Hz
P04.08
V/F
voltage 3 of
motor 1
0.0%~110.0%
00.0%
P04.09
V/F slip
compensation
gain of motor 1
0.0~200.0%
100.0%
P04.10
Vibration
control factor
at low
frequency of
motor 1
0~100
10
P04.11
Vibration
control factor
at high
frequency of
0~100
10

Table of Contents