Goodrive300-19 series open loop vector inverter special for hosit Basic operation instruction
-135-
Function
code
Name
Detailed instruction of parameters
Default
value
P00.00
Speed
control mode
1: Sensorless vector control mode 1
2: SVPWM control mode
1
P03.11
Torque
setting
method
0: Torque control is invalid
1: Keypad setting torque (P03.11)
2: Analog AI1 setting torque (100% corresponds to three
times of the rated current of the motor)
3: Analog AI2 setting torque (the same as above)
4: Analog AI3 setting torque (the same as above)
5: Pulse frequency HDI setting torque (the same as above)
6: Multi-step torque setting (the same as above)
7: Modbus communication setting torque (the same as
above)
8~10: Reserved
0
P03.12
Keypad
setting torque
-300.0%~300.0% (rated current of the motor)
50.0%
P03.13
Torque
reference
filter time
0.000~10.000s
0.010s
P03.14
Upper
frequency of
forward
rotation in
torque control
0: Keypad (P03.16)
1: AI1 (100% corresponds to the Max. frequency)
2: AI2 (the same as above)
3: AI3 (the same as above)
4: Pulse frequency HDI setting upper-limit frequency (the
same as above)
5: Multi-step setting upper-limit frequency (the same as
above)
6: Modbus communication setting upper-limit frequency
(the same as above)
7~9: Reserved
0
P03.15
Upper
frequency of
0: Keypad (P03.17)
1: AI1 (100% corresponds to the Max. frequency)
0