Goodrive300-19 series open loop vector inverter special for hosit Basic operation instruction
-144-
Stand by
Running state before
power off
0
1
P01.21
(Restart after power off selection)
Waiting time of restart
after power off > P01.22
0
1
2
Stopping
Running
0
1
P01.18
(Running protection of powering on terminal selection)
Restart delay time
> P01.23
N
Y
Y
N
Restart after
power off
Running
Stopping
FWD/REV
Whether the running
command terminal is valid
N
Running
Y
P00.01
Running command channel
Keypad
Communication
Terminal
3. The starting logic figure of starting after the automatic fault reset
Inverter fault
In running
Fault reset times of the
inverter <P08.28
Interval time of
automatic fault reset of
the inverter >P08.29
Fault reset and the
inverter starts to run.
Display fault
code and the
inverter stops.
N
N
Y
Y
Relative parameters list:
Function
code
Name
Detailed instruction of parameters
Default
value
P00.01
Running
command
channel
0: Keypad running command channel (LED off)
1: Terminal running command channel (LED flickering)
2: Communication running command channel (LED on)
1
P00.11
ACC time 1
0.0~3600.0s
Depend
on model
P00.12
DEC time 1
0.0~3600.0s
Depend
on model
P01.00
Start mode
0: Start-up directly
1: Start-up after DC braking
2: Start-up after speed tracing
0
P01.01
Starting
0.00~50.00Hz
0.50Hz