Goodrive300-19 series open loop vector inverter special for hosit Basic operation instruction
-187-
by the hierarchical reference of multi-step speed terminals. The mode supports up to 6 different
speed levels. The hierarchical contact can be connected to the selected digital input S terminal and
the corresponding speed reference is given by mulit-step speed hierarchical reference 1~5
(P19.06~P19.11). The mode does not need zero position detection or detect hierarchical joystick
fault.
The parameters of hierarchical remote control mode are as follows:
Function
code
Name
Function
selection
Function instruction
P00.01
Running command channel
1
Terminal running command
channel (LED flickering)
P00.06
A frequency command
13
Hierarchical multi-step speed
reference
P05.01
S1 terminal function selection
1
Forward rotation operation (FWD)
P05.02
S2 terminal function selection
2
Reverse rotation operation (REV)
P05.03
S3 terminal function selection
7
Fault reset (RET)
P05.04
S4 terminal function selection
61
Hierarchical reference terminal 1
P05.05
S5 terminal function selection
62
Hierarchical reference terminal 2
P05.06
S6 terminal function selection
63
Hierarchical reference terminal 3
P06.03
Relay RO1 output
5
Fault output
P06.04
Relay RO2 output
34
Brake control output
P06.14
AO1 output
0
Running frequency
P06.15
AO2 output
5
Current output
P19.01
Brake and contactor control
selection
0x01
Brake is controlled by inverter
7.16.6 Electromotion potentiometer mode
The wiring diagram of electromotion potentiometer mode is as follows: