-45-
Detailed instruction of parameters
(“LOCAL/REMOT” on);
The running command is controlled by the upper
computer via communication.
This parameter is used to set the maximum output
frequency of the inverter. Users should pay attention
to this parameter because it is the foundation of the
frequency setting and the speed of acceleration and
deceleration.
Setting range: P00.04~400.00Hz
Upper limit
of running
frequency
The upper limit of running frequency is the upper limit
of output frequency of the inverter which is lower than
or equal to the maximum frequency.
Setting range: P00.05~P00.03 (Max. output
frequency)
Lower limit
of running
frequency
The lower limit of running frequency is that of output
frequency of the inverter.
The inverter runs at the lower limit frequency if the set
frequency is lower than the lower limit one.
Note: Max. output frequency ≥ Upper limit
frequency ≥ Lower limit frequency
Setting range: 0.00Hz~P00.04 (Upper limit of running
frequency)
Note: Frequency A and frequency B cannot use the
same frequency setting mode. The frequency source
can be set by P00.09.
0:Keypad
Modify the value P00.10 (set the frequency by
keypad) to modify the frequency by the keypad.
1: AI1
2: AI2
3: AI3
Set the frequency by analog input terminals.
Goodrive300-19 series inverters provide 3 ways