Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-46-
Function
code
Name
Detailed instruction of parameters
Default
value
Modify
analog input terminals as the standard configuration,
of which AI1/AI2 are the voltage/current option
(0~10V/0~20mA) which can be shifted by jumpers;
while AI3 is voltage input (-10V~+10V).
Note: When analog AI1/AI2 select 0~20mA input,
the corresponding voltage of 20mA is 10V.
100.0% of the analog input setting corresponds to the
maximum frequency (P00.03) in forward direction and
-100.0% corresponds to the maximum frequency in
reverse direction (P00.03)
4: High-speed pulse HDI setting
The frequency is set by high-speed pulse terminals.
Goodrive300-19 series inverters provide 1 high speed
pulse input as the standard configuration. The pulse
frequency range is 0.0~50.00kHz.
100.0% of the high-speed pulse input setting
corresponds to the maximum frequency in forward
direction (P00.03) and -100.0% corresponds to the
maximum frequency in reverse direction (P00.03).
Note: The pulse setting can only be input by
multi-function terminals HDI. Set P05.00 (HDI
input selection) to high speed pulse input, and set
P05.49 (HDI high speed pulse input function
selection) to frequency setting input.
5: Reserved
6: Multi-step speed running setting
The inverter runs at multi-step speed mode when
P00.06=6 or P00.07=6. Set P05 to select the current
running stage, and set P10 to select the current
running frequency.
The multi-step speed has the priority when P00.06 or
P00.07 does not equal to 6, but the setting stage can
only be the 1~15 stage. The setting stage is 1~15 if