Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-93-
Detailed instruction of parameters
ratio of
dropping
control
several inverters drive one load.
Setting range: 0.00~50.00Hz
Goodrive300-19 series supports the shift between
two motors. This function is used to select the shifting
channel.
0x00~0x14
LED ones: shifting channel
0: terminal shifting; digital terminal is 35
1: Modbus communication shifting
2~4: Reserved
LED tens: shifting enabling in operation
0: Disabled
1: Enabled
FDT1
electrical
level
detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical level, the
multi-function digital output terminals will output the
signal of “frequency level detect FDT” until the output
frequency decreases to a value lower than (FDT
electrical level—FDT retention detection value) the
corresponding frequency, the signal is invalid. Below
is the waveform diagram:
Setting range of P08.32: 0.00Hz~P00.03 (the Max.
frequency)
FDT1
retention
detection
value
FDT2
electrical
level
detection
value
FDT2
retention
detection
value