Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-97-
Detailed instruction of parameters
terminals
frequency
changing
ratio
DOWN
terminals
frequency
changing
ratio
Frequency
setting at
power loss
0x000~0x111
LED ones: Action selection when power off.
0: Save when power off
1: Clear when power off
LED tens: Action selection when Modbus set
frequency off
0: Save when power off
1: Clear when power off
LED hundreds: Reserved
High bit of
initial power
consumption
This parameter is used to set the original value of the
power consumption.
Original value of power consumption
=P08.48*1000+P08.49
Setting range of P08.48: 0~59999 kWh(k)
Setting range of P08.49: 0.0~999.9 kWh
Low bit of
initial power
consumption
This function code is used to enable magnetic flux.
0: Invalid.
100~150: The bigger the coefficient, the stronger the
braking is.
This inverter is used to increase the magnetic flux to
decelerate the motor. The energy generated by the
motor during braking can be converted into heat
energy by increasing the magnetic flux.
The inverter monitors the state of the motor