Goodrive300-19 series open loop vector inverter special for hosit Function parameters
-96-
Detailed instruction of parameters
adjustment is valid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: Valid for all frequency setting manner
2: Invalid for multi-step speed when multi-step speed
has the priority
LED hundreds: action selection during stopping
0: Setting is valid
1: Valid during running, clear after stopping
2: Valid during running, clear after receiving the stop
command
LED thousands: ∧/∨ key and digital potentiometer
integral function
0: The integral function is valid
1: The integral function is invalid
Integral ratio
of keypad
potentiometer
UP/DOWN
terminals
control
0x000~0x221
LED ones: frequency enable selection
0: UP/DOWN terminals setting is valid
1: UP/DOWN terminals setting is invalid
LED tens: frequency control selection
0: Only valid when P00.06=0 or P00.07=0
1: All frequency means are valid
2: When the multi-step speed has the priority, it is
invalid to the multi-step speed
LED hundreds: action selection during stopping
0: Setting is valid
1: Valid during running, clear after stop
2: Valid during running, clear after receiving the stop
command