Goodrive35 Series Closed-loop Vector Control VFD Basic operation instruction
147
Function
code
Name
Detailed instruction of parameters
Default
value
1: Synchronous motor
P02.02
Rated frequency of
asynchronous motor 1
0.01 HzP00.03 (max. output frequency)
50.00
P02.04
Rated voltage of
asynchronous motor 1
01200 V
Depend on
model
P04.00
Motor 1 V/F curve setting
0: Straight line V/F curve
1: Multi-dots V/F curve
2: 1.3
th
power low torque V/F curve
3: 1.7
th
power low torque V/F curve
4: 2.0
th
power low torque V/F curve
5: Customized V/F (V/F separation)
0
P04.01
Torque boost of motor 1
0.0%: (automatic) 0.1%10.0%
0.0%
P04.02
Torque boost close of
motor 1
0.0%50.0% (rated frequency of motor 1
frequency)
20.0%
P04.03
V/F frequency 1 of motor 1
0.00 HzP04.05
0.00 Hz
P04.04
V/F voltage 1 of motor 1
0.0%110.0%
00.0%
P04.05
V/F frequency 2 of motor 1
P04.03P04.07
00.00 Hz
P04.06
V/F voltage 2 of motor 1
0.0%110.0%
00.0%
P04.07
V/F frequency 3 of motor 1
P04.05P02.02 or P04.05P02.16
00.00 Hz
P04.08
V/F voltage 3 of motor 1
0.0%110.0%
00.0%
P04.09
V/F slip compensation
gain of motor 1
0.0200.0%
100.0%
P04.10
Vibration control factor at
low frequency of motor 1
0100
10
P04.11
Vibration control factor at
high frequency of motor 1
0100
10
P04.12
Vibration control threshold
of motor 1
0.00 HzP00.03 (max. output frequency)
30.00 Hz
P04.13
Motor 2 V/F curve setting
0: Straight line V/F curve
1: Multi-dots V/F curve
2: 1.3
th
power low torque V/F curve
3: 1.7
th
power low torque V/F curve
4: 2.0
th
power low torque V/F curve
5: Customized V/F (V/F separation)
0
P04.14
Torque boost of motor 2
0.0%: (automatic) 0.1%10.0%
0.0%
P04.15
Torque boost close of
motor 2
0.0%50.0% (rated frequency of motor 1)
20.0%