Goodrive35 Series Closed-loop Vector Control VFD Fault tracking
202
Inverter module
overheated
The time of overload running is
too long.
Lower the ambient temperature
SI external fault input terminals
act
Check the external device input
The baud rate setting is
incorrect.
Fault occurs to the
communication wiring.
Communication address is wrong.
There is strong interference to
the communication.
Set proper baud rate
Check the communication
connection distribution
Set proper communication address.
Chang or replace the connection
distribution or improve the
anti-interference capability.
The connection of the control
board is not good
Hall components is broken
The modifying circuit is
abnormal.
Check the connector and re-plug
Change the Hall
Change the main control panel
The motor capacity does not
comply with VFD capability
The rated parameter of the motor
does not set correctly.
The offset between the
parameters from autotune and
the standard parameter is huge
Autotune overtime
Change the VFD mode
Set the rated parameter according to
the motor name plate
Empty the motor load and re-identify
Check the motor connection and set
the parameter.
Check if the upper limit frequency is
above 2/3 of the rated frequency.
Error of controlling the write and
read of the parameters
Damage to EEPROM
Press STOP/RST to reset
Change the main control panel
PID feedback
outline fault
PID feedback offline
PID feedback source disappear
Check the PID feedback signal
Check the PID feedback source
Brake circuit fault or damage to
the brake pipes
External brake resistor is
insufficient
Check the brake unit and , change
new brake pipe
Increase the brake resistor
The actual running time of the
VFD is above the internal setting
running time.
Ask for the supplier and adjust the
setting running time.
VFD will report overload
pre-alarm based on the set value.
Check the load and the overload
pre-alarm threshold.
The connection of the keypad
Check the keypad wires and ensure