SV-DA200 series AC servo drives                                                                         Faults and solutions 
‐141‐
P4.30 Setting value
Action 
During deceleration  After stopping 
[0]  Coast to stop  Keep the inertia operation state 
1  Dynamic brake to stop  Keep the inertia operation state 
2  Dynamic brake stop  Dynamic braking state 
3  External dynamic brake acts  Dynamic braking state 
Note: 
1. When P4.30 is set to 1, the dynamic brake works when motor speed is higher than the value 
of P3.58 and does not work otherwise. After motor stops, dynamic brake will stop working. 
2. If the running speed of servo motor is faster than rated speed, do not use the dynamic brake. 
If the running speed is high with large inertia load, please use the dynamic brake with caution. 
Do not start the dynamic brake frequently; otherwise, damage may occur to the servo drive.   
P4.30 
Data size  16bit  Data format  DEC 
Modbus address  1860,1861  CANopen address  0x241E,0x00
 
P4.31  Max. speed limit 
Setting range Default Unit  Available mode
0~20000  5000 r/min  P S T F
This parameter can be used to set the highest running speed of servo motor. If the absolute value 
of the speed command is  larger than the value of  this  parameter, the magnitude of  the actual 
speed setting will be limited by this parameter; the direction is the same with that of the original 
speed command. This parameter is active in all modes. 
Note: The default value of this parameter is related to the power level of the drive. 
P4.31 
Data size  16bit  Data format  DEC 
Modbus address  1862,1863  CANopen address  0x241F,0x00 
 
P4.32  Overspeed level 
Setting range Default Unit  Available mode
0~20000  6000 r/min  P S T F
This parameter is used to set the overspeed level of the servo motor. When the rotation speed of 
the motor exceeds this setting speed, overspeed fault alarm will be reported.   
Note: The default value of this parameter is related to the power level of the drive. 
P4.32 
Data size  16bit  Data format  DEC 
Modbus address  1864,1865  CANopen address  0x2420,0x00
 
P4.33 
Pulse range of position 
deviation 
Setting range Default Unit  Available mode
0~2
27
  100000 reference unit P F
This parameter is used to set the alarm threshold for the position deviation (Er22-0). In position 
or  fully-closed  loop  mode,  when  the  number  of  retention  pulses  exceeds  this  setting  value, 
position error fault will be alarmed.   
P4.33 
Data size  32bit  Data format  DEC 
Modbus address  1866,1867  CANopen address  0x2421,0x00 
 
P4.34
1
 
Brake overload detection 
selection 
Setting range Default Unit  Available mode
0~2  0  -  P S T F