INDOOR UNITS
3-32
TC-15001-rev.3
Ŷ )UHH]H3URWHFWLRQ&RQWUROGXULQJ&RROLQJRU'U\2SHUDWLRQ
Power Supply
No
Yes
No
No
Yes
Yes
Cooling or Dry Operation
Cooling or Dry Operation
> 32
o
F(0
o
C)
< 32
o
F(0
o
C)
> 58
o
F(14
o
C)
< 58
o
F(14
o
C)
Gas or Liquid Pipe
Surface Temp. of
Indoor Heat Exchanger
Is it continuous for
more than 3 min.?
Is it continuous
for more than 3 min.?
(6 min. in case of
Dry Operation)
Is compressor
operated for more than
15 min?*
* The check interval differs
depending on the conditions.
I.U. Electronic Expansion Valve:
Completely Closed
No
No
Yes
MIF Operation at Set Fan Speed
(In case of Dry Operation,
MIF Operation: OFF for 6 min.)
Either Gas or Liquid Pipe
Surface Temp. of
Indoor Heat Exchanger
Yes
Elapsed Time:
15 min.
Pipe Surface
Temp.
*2)
> 36
o
F(2
o
C)
I.U.: Indoor Unit
a
a
*2): Pipe Surface Temp.
NOT adopted at .
MIF : Motor for Indoor Fan

Table of Contents

Other manuals for Johnson Controls (H,Y,C)IDM012B21S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls (H,Y,C)IDM012B21S and is the answer not in the manual?

Johnson Controls (H,Y,C)IDM012B21S Specifications

General IconGeneral
BrandJohnson Controls
Model(H, Y, C)IDM012B21S
CategoryAir Conditioner
LanguageEnglish

Related product manuals