INDOOR UNITS
TC-15001-rev.3
3-61
Models: (H,Y)IC4012B21S, (H,Y)IC4015B21S, (H,Y)IC4018B21S, (H,Y)IC4024B21S,
(H,Y)IC4030B21S and (H,Y)IC4036B21S
3.2.7 Operation Space
(Unit Height in False Ceiling)
Clearance
Down Slope
Gradient: 1/25 to 1/100
Condensate Piping
012 to 018 Type: 9-3/4 (248)
024 to 036 Type:11-23/32 (298)
Min. 13/32 (10)
Piping Connection Piping Connection Piping Connection
Min.
3-15/16
Min.
3-15/16
Min.
19-11/16
Min.
19-11/16
Min.
3-15/16
Min.
3-15/16
Min.
19-11/16
Min.
3-15/16
Min.
3-15/16
Min.
19-11/16
Min.
118-1/8
Min.
94-1/2
(2400)
Unit: inch (mm)
Service Space
(500) (500)
(100)
(100)
(3000)(500)
(500)
(100)
(100)
(100)
(100)
Distance from Wall Side
Piping
Connection
Side
Min. 59-1/16 (1500)
Min. 59-1/16 (1500)
Min. 59-1/16 (1500)
Min. 59-1/16 (1500)
3.2.8 Sensible Heat Factor (SHF)
Model SHF *1
(H,Y)IC4012B21S 0.77
(H,Y)IC4015B21S 0.78
(H,Y)IC4018B21S 0.89
(H,Y)IC4024B21S 0.81
(H,Y)IC4030B21S 0.83
(H,Y)IC4036B21S 0.83
NOTE:
1. SHF is based on combinations within the VRF system and the following conditions:
Cooling Operation Conditions
Indoor Air Inlet Temperature: 80
o
F DB (26.7
o
C DB)
67
o
F WB (19.4
o
C WB)
Outdoor Air Inlet Temperature: 95
o
F DB (35.0
o
C DB)
Piping Length: 24 ft. 7-3/16 in. (7.5m)
Piping Lift: 0 ft. (0m)

Table of Contents

Other manuals for Johnson Controls (H,Y,C)IDM012B21S

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls (H,Y,C)IDM012B21S and is the answer not in the manual?

Johnson Controls (H,Y,C)IDM012B21S Specifications

General IconGeneral
BrandJohnson Controls
Model(H, Y, C)IDM012B21S
CategoryAir Conditioner
LanguageEnglish

Related product manuals