IFC-3030 Programming Manual — P/N 52025:C 08/05/2005 103
Abort Switches Releasing Applications
2. The FACP programmed Delay Time begins its 15 second countdown. The Manual Release
Delay switch is pulled when the FACP Delay Timer has counted down to 8 seconds. The 8
seconds remaining in the countdown are overridden by the 10-second delay initiated by the
Manual Delay switch. In this example, the total time elapsing from FACP countdown initiation
to agent release is 17 seconds, more than the original 15 second FACP Delay Timer
countdown.
3. The FACP programmed Delay Time is not running (as would happen if the releasing station
were pulled before an alarm registered). The Manual Release Delay Switch is activated by the
pull station. Agent release will occur in 10 seconds.