IFC-3030 Programming Manual — P/N 52025:C 08/05/2005 43
Point Program Program
Detector Point Programming (3)
Press the MORE soft key on the Detector Point Programming (2) screen to display this screen.
Figure 3.30 More Detector Point Programming (3) Screen
Soft Keys
PREALARM: Press to select ALERT or ACTION for the Prealarm function. Refer to the section on
Prealarm in Appendix D, “AWACS™ Applications” for a description of Alert and Action.
SILENCEABLE: This field determines whether the user can manually silence a detector’s
activated sounder/relay base. Values are as follows:
3.4.2 Module Point
Module point programming screens will display if a module point address is entered at the Point
Programming Menu (see Figure 3.23 on page 37 ).
NO Not manually silenceable
YES - RESOUND FIRE Silenceable, resound on fire alarm events Network and Local Resound
YES - RESOUND SUPERV Silenceable, resound on supervisory events Network and Local Resound
YES - NO RESOUND Silenceable, does not resound
DETECTOR POINT PROGRAMMING
L03D123
PREALARM:ALERT
SILENCEABLE:NO
ACCEPT
BACK