IFC-3030 Programming Manual — P/N 52025:C 08/05/2005 25
Panel Program Program
AUTO SILENCE: Press to enter a value of OFF (no Auto Silence Timer), or a value of 10, 15 or 20
minutes. This global software timer functions like pressing the SIGNAL SILENCE key. For
example, if a value of 10 is entered, the control panel will silence all active outputs programmed as
silenceable after ten minutes. Default: 0FF
NOTE: This value must be 20 minutes for ULC installations.
VERIFY=PREALARM: Press this soft key to enter Yes or No for displaying Prealarm during alarm
verification. Default: NO
3.2.5 Panel Timers (Menu 2)
Press the MORE soft key on the Panel Timers Menu 1 screen to display the following screen.
Figure 3.9 Panel Timers (Menu 2) Screen
Soft Keys
PAS: Press to toggle between the choices of OFF or ON for PAS (Positive Alarm Sequence). Refer
to Appendix C, “Special Zone Outputs” for an explanation of this option. Default: OFF
PRESIGNAL DELAY: Press to enter a value of 00:00 (OFF) or a value of 1:00 to 3:00 minutes (in
the format MM:SS, where MM= minutes, SS=seconds). This feature initially causes alarm signals
to sound only in specific areas, monitored by qualified personnel. This allows delay of the alarm for
up to 3 minutes after the start of alarm processing. Refer to Appendix C, “Special Zone Outputs”
for further explanation of this option. Default: 3:00
DEFAULT TIMERS: Press this soft key to activate default settings for the following:
ACCEPT: Press this soft key to save the information entered on this screen and return to the
previous screen.
Program setting for: Default:
Verify Time 30 seconds
Max. Verify 20
AC Fail Delay 8 hours
SIlence Inhibit 0 (disabled)
Auto Silence Off
Verify=Prealarm No
PAS OFF
Presignal Delay 3 minutes
PANEL TIMERS
PAS: OFF
PRESIGNAL DELAY: MM:SS
DEFAULT TIMERS
ACCEPT
BACK

Table of Contents

Other manuals for Johnson Controls IFC-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFC-3030 and is the answer not in the manual?

Johnson Controls IFC-3030 Specifications

General IconGeneral
BrandJohnson Controls
ModelIFC-3030
CategoryControl Panel
LanguageEnglish

Related product manuals