IFC-3030 Programming Manual — P/N 52025:C 08/05/2005 69
Clear Verify Counters Alter Status
OCCUPIED ALARM: The type of alarm/prealarm will display based on which soft key was
pressed in the previous screen. For example, in the screen above, OCCUPIED ALARM displays
because the OCCUPIED ALARM SENSITIVITY: soft key was pressed.
The detector sensitivity values display below the soft key. Select a value by pressing the soft key
until the desired value appears in the underlined field.
ACCEPT: Press to accept the change made on this screen, and to return to the previous screen.
4.4 Clear Verify Counters
The Clear Verify Counters screen lets you clear all counters for detectors selected for Alarm
Verification on the FACP. It displays when the “CLEAR VERIFY COUNTERS” soft key is pressed
on the Alter Status Menu screen.
Figure 4.7 Clear Verify Counters Screen
Soft Keys
CLEAR COUNTERS: Press this soft key to clear all verification counters.
4.5 Clear History
This screen is displayed when the CLEAR HISTORY soft key is pressed on the Alter Status Menu
screen. It brings the user to a command screen, where the type of history may be selected for
clearing.
LAKEVIEW GENERAL HOSPITAL
SYSTEM NORMAL
10:22:34A FRI SEP 24, 2004
ALTER STATUS MENU
LAKEVIEW GENERAL HOSPITAL
THIS WILL CLEAR ALL VERIFY COUNTERS
CLEAR COUNTERS
BACK

Table of Contents

Other manuals for Johnson Controls IFC-3030

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls IFC-3030 and is the answer not in the manual?

Johnson Controls IFC-3030 Specifications

General IconGeneral
BrandJohnson Controls
ModelIFC-3030
CategoryControl Panel
LanguageEnglish

Related product manuals