30 IFC-3030 Programming Manual — P/N 52025:C 08/05/2005
Program Panel Program
3.2.8 Supervision
From the Panel Program Menu (1), select SUPERVISION to display the following screen.
Figure 3.13 Supervision Screen
Soft Keys
MAIN POWER SUPPLY AC FAIL ADDRESS: Press to enter the “Monitor AC Fail” (base plus
one) address of the main power supply. Refer to the main power supply manual for complete
addressing information. Type in the address using the keypad.
The LCD backlight will turn off when this power supply experiences AC failure (see BACKLIGHT
in “LCD Programming” on page 26).
PRINTER: Press to scroll through the types of printer supervision: NONE, 40-COLUMN,
40-COLUMN SUPERVISED, 80-COLUMN, 80-COLUMN SUPERVISED, 40 GRAPHIC, 80
GRAPHIC, 80 GRAPHIC SUPERVISED. The printer will not be active if NONE is selected. If a
SUPERVISED selection is made, the printer will be supervised. Default: NONE
NOTE: When changing from an 80-column or 80-column supervised to an 80 graphic or 80
graphic supervised printer (or vice-versa) , settings must be changed at the printer. Refer to this
panel’s installation manual for the settings.
AUXILIARY TROUBLE REPORTING: Press to toggle between Yes and No. Choose Yes if a
trouble bus cable has been attached at J5 of the JCPU-3030. Default: NO
TAMPER INPUT: Press the soft key to toggle between Yes, No, and AKS-1.
Yes/No reports (YES) or does not report (NO) a tamper situation at the panel cabinet door (as
determined by an STS-1 tamper switch connected as shown in this panel’s installation
manual).
AKS-1 should be selected when there is an AKS-1 key switch connected to the panel cabinet
door (which allows the operator to use Signal Silence, Reset, Drill and Acknowledge functions
when a key turns the lock to “Enable”). Default: NO
ACCEPT: Press to save changes and return to previous menu.
SUPERVISION
MAIN PS AC FAIL ADDRESS: LXXMXXX
PRINTER: 80-COLUMN
AUXILIARY TROUBLE REPORTING:NO ACCEPT
TAMPER INPUT: NO BACK