22 IFC-3030 Programming Manual — P/N 52025:C 08/05/2005
Program Panel Program
DISPLAY ADDRESS: Press this soft key to toggle between Yes and No. Choose Yes to display all
point address information at the top of event screens and in printouts. Choose No to suppress
address information display and printing. Default: Yes
REMINDER MENU: Press this soft key to bring up the Reminder Menu screen.
ACCEPT: Press this soft key to save the information entered on this screen.
MORE: Press this key to progress to the second Panel Settings screen.
Figure 3.6 Panel Settings (2) Screen
Soft Keys
LCM LOCAL MODE: Press this soft key to toggle between Yes and No. Enter Yes to enable all SLCs
to participate in local mode. When enabled, all LCMs will operate together in a limited fashion
when communication is lost with the IFC-3030 CPU. Inputs on LCM loops (and associated LEM
loops, if installed) will activate outputs on all loops
for those inputs and outputs that have been set with point programming to participate in local
mode, and
when type codes are the same point type: that is, an input with a fire type code will activate
an output with a fire type code.(Refer to Appendix G, “Type Codes”, on page 133 for point
types).
Default: NO
PANEL CIRCUIT BELL CODING: Press to toggle between MARCH and TEMPORAL. This is a
global setting: ZF8 must be entered in the zone map of any panel circuit point that will participate
in this coding. Refer to “Coding Functions for Panel Circuit Outputs” on page 114 for more
information. Default: MARCH
DCC PARTICIPATION: Press this key to program the panel for DCC (Display and Control Center)
participation. This network function ensures that one location at a time is in command of the
Acknowledge, System Reset, Signal Silence and Drill functions. Default: NO
CAUTION:
On systems utilizing the DCC function, all locations that can participate in DCC should be set to
YES.
PANEL SETTINGS
LCM LOCAL MODE: YES
PANEL CIRCUIT BELL CODING: MARCH
DCC PARTICIPATION: NO
LOCAL SETTINGS ACCEPT
DEFAULT SETTINGS BACK
!