28 IFC-3030 Programming Manual — P/N 52025:C 08/05/2005
Program Panel Program
POINT PROGRAMMING: Press this soft key to proceed to the ACS Point Programming screen.
ACCEPT: Press this soft key to save all the changes made and return to the previous screen (Panel
Program).
ACS Point Programming
ACS Point Programming can be reached by pressing POINT PROGRAMMING at the ACS
Programming screen. This screen allows the programmer to assign a mode and sources to each
annunciator point at the annunciator address. One ACS input may be used to control multiple panel
circuit or SLC output modules by listing the output points in the SOURCE fields. This feature
applies to the following Types: 64PT, 64SYS, 96PT, and 96SYS.
Figure 3.12 ACS Point Programming Screen
Soft Keys
POINT: Press this soft key to enter the ACS point number. The format is AxxPyy, where A is the
two-digit device address, P is the two-digit point number. Enter a leading zero for one-digit
numbers.
96SYS 96 point annunciation, with first 8 points reserved
UDACT UDACT, first address. Any additional UDACT
annunciator addresses should be programmed as
64PT and be sequential.
TM4 TM-4
AMG AMG
FSCS Smoke control modules set for FSCS mode
HVAC Smoke control modules set for HVAC mode
UZC Universal Zone Coder, first address. Any additional
UZC annunciator addresses should be programmed
as 64PT and be sequential.
NOTE: Panel circuit or SLC output modules with releasing Type IDs may not be listed in the
annunciator source fields.
NOTE: This FACP supports ACM-24AT/ACM-48A annunciators and their expanders with either
64 or 96 points at an address, as well as ACM-16AT/ACM-32A/LDM-32 annunciators with 64
points at an address.
ACS POINT PROGRAMMING
POINT: A27P04
MODE: CONTROL
SOURCE: L01M037 L01M038
P10.2
NEXT ACCEPT
PREVIOUS BACK