48 IFC-3030 Programming Manual — P/N 52025:C 08/05/2005
Program Point Program
Point Programming (1)
The Panel Circuit Point Programming screen will display if a panel circuit point address is entered
at the Point Programming Menu (see Figure 3.23 on page 37 ).
Figure 3.35 Panel Circuit Point Programming (1) Screen
Soft Keys
PANEL MODULE TYPE: Press the soft key to toggle between MONITOR, CONTROL-CRM,
CONTROL-ICM. Select MONITOR for IZM-8RK/IZE-A modules, CONTROL-CRM for
CRM-4RK/CRE4 modules, and CONTROL-ICM for ICM-4RK/ICE-4 modules.
TYPE CODE LABEL: Press this soft key to scroll through the point Type Code choices: stop at
the appropriate selection.
POINT LABEL: Press this soft key to place the cursor at this field. Type in a 20-character
maximum point label that will appear in message formats. If no entry is made, the field will default
to the point address.
EXTENDED LABEL: Press to place the cursor at this field. Type in a 12-character maximum
extended label to further define the location or nature of the point.
MORE: Press to proceed to the next screen for more point programming.
ACCEPT: Press to save entries made on this screen.
PANEL CKT POINT PROGRAMMING
P11.2
PANEL MODULE TYPE: MONITOR
TYPE CODE LABEL:HEAT DETECT
MORE
POINT LABEL: ACCEPT
EXTENDED LABEL:
BACK