IFC-3030 Programming Manual — P/N 52025:C 08/05/2005 63
Autoprogram Menu Program
Figure 3.54 Autoprogram Confirmation Screen (Double Address)
Display
The SLC loop number and device address are displayed where the Autoprogram has found more
than one detector or module with the same address.
Soft Keys
ACCEPT: Pressing this soft key acknowledges that the programmer has been informed of the
double address. Autoprogram will not make a modification to the database for this point. The
installer must correct this problem.
AUTOPROGRAM CONFIRMATION
DOUBLE ADDRESS FOUND AT LXXDXXX
ACCEPT
BACK