Art. No. SC 1000 KNX
i The internal timer of the device also needs information about the current weekday in order
to process the switching times. Depending on the date set, the day is determined
automatically by means of the internal calendar and the timer is made available. The day
transmitted in the KNX time telegram in compliance with DPT 10.001 is irrelevant and is
discarded by the device.
Time and date can be displayed in different places. Thus, it is possible to display the time on the
start page and the date in the status line on display pages of the main navigation. The display of
the date and time can be formatted differently and thus tailored to the user's specific
requirements. Additionally, the date and time can be displayed or hidden as required.
The display format and visibility of date and time can be edited in the ETS or in the
administration area locally on the device. Consequently, the configuration can take place in the
ETS as part of the presetting and adapted by a menu operation at any time afterwards. In the
ETS, the parameters "Display date" and "Display time" in the parameter node "Display" define
the corresponding display formats. In the setting "no display", the date or time are not displayed
in the aforementioned places.
Similarly, the same characteristics of date and time can be edited on the display pages
(figure 65). The required display format is selected by finger pressure on the corresponding
formatting in the display Display (Marking: X = deselected, > = selected). The setting is
included in the status line via the "Save >" button. The display then returns to the system
page. Alternatively, settings can be discarded by pressing the "Z Cancel" button in the status
line. The display then returns to the system page without saving the setting.
i Hiding date or time does not effect the system clock and thus does not effect the
processing of the switching times by the timer either. If date or time are not displayed, the
internal system clock still continues running normally.
i Regardless of the display format selected for the time, switching times of the internal timer
of the device in the ETS or locally on the device in the menus of the timer must be specified
in 24-hour format.
Page 134 of 347
Software "Smart Control 501511"
Functional description