Art. No. SC 1000 KNX
evaluated and displayed. The measured
value must be made available to the
device via the bus in compliance with
KNX DPT 9.xxx. The measured value
may possibly be converted and adapted
to the required display format according
to the setting of the parameter "Gain",
"Offset", "Number of integer digits" and
"Number of decimal places".
Name Value 1,
free text with a maximum
variable length of 18
characters
A text name can be assigned here to the
first measured value (e.g. "Temperature
Loggia"), which is displayed on the
display page of the weather station for
identification. The possible length of the
text depends on the set size of the
letters or numbers entered in the entry
field and can vary. A text with a
maximum of 18 characters can be
entered.
Display unit Yes
No
The value in the display can optionally
be supplemented by a unit (setting:
Yes). The text for the value unit ("°C" for
example) is specified by the parameter
"Text for unit". In the setting "No", the
value display is not supplemented by a
unit.
Text for unit free text with a max. of 5
characters, no text is
entered in the presetting
This parameter specifies the unit for the
value display. A text with a maximum of
5 characters can be entered.
This parameter is only visible when the
external value is to be supplemented by
a unit text.
Amplification
(-10,000,000...
10,000,000)
-10,000,000...
1.0
...10,000,000
When a value is received from the bus,
the device calculates the value display
based on the gain factor and value
offset (value display = bus value x gain
+ offset). This parameter specifies the
gain of the value. The gain can be
positive as well as negative.
Offset
(-10,000,000...
10,000,000)
-10,000,000...
0.0
...10,000,000
When a value is received from the bus,
the device calculates the value display
based on the gain factor and value
offset (value display = bus value x gain
+ offset). This parameter defines the
offset (shift) of the value. The offset can
be positive as well as negative.
Number of integer digits 0...3...9 This parameter defines how many digits
the status value has in the display.
Page 276 of 347
Software "Smart Control 501511"
Parameters