Art. No. SC 1000 KNX
Rocker X.2: no function
Rocker X.1: no function /
Rocker X.2: 0...255
Rocker X.1: no function /
Rocker X.2: 0...100 %
Value, rocker 1.1
(0...255)
0...255 Depending on the "Button arrangement"
parameter, this parameter defines the
object value when the top (or left-hand)
rocker is pressed. Visible only if
"Function = 0…255"!
Value, rocker 1.2
(0...255)
0...255 Depending on the "Button arrangement"
parameter, this parameter defines the
object value when the bottom (or right-
hand) rocker is pressed. Visible only if
"Function = 0…255"!
Value, rocker 1.1
(0...100 %)
0...100 Depending on the "Button arrangement"
parameter, this parameter defines the
object value when the top (or left-hand)
rocker is pressed. Visible only if
"Function = 0...100 %"!
Value, rocker 1.2
(0...100 %)
0...100 Depending on the "Button arrangement"
parameter, this parameter defines the
object value when the bottom (or right-
hand) rocker is pressed. Visible only if
"Function = 0...100 %"!
Value adjustment by
long button-press
enabled
disabled
If value adjustment by long button-press
is enabled, the ETS shows further
parameters.
Value adjustment begins, when the
button is held down for more than 5 s. In
this case, the respective status LED
flashes as a sign that a new telegram
has been transmitted.
Starting value in case of
value adjustment
Same as configured value
Same as value after last
adjustment
Same as value from
communication object
Value adjustment can begin with
different starting values.
In the setting "Same as parameterised
value", after each long press the
pushbutton sensor always starts with the
value programmed in the ETS.
In the setting "Same as value after last
adjustment", after a long press the
pushbutton sensor starts with the value
transmitted by itself or by another device
with this group address as the last
value.
In the setting "Same as value from
Page 317 of 347
Software "Smart Control 501511"
Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jung Smart Control SC 1000 KNX and is the answer not in the manual?

Jung Smart Control SC 1000 KNX Specifications

General IconGeneral
BrandJung
ModelSmart Control SC 1000 KNX
CategoryController
LanguageEnglish

Related product manuals