Art. No. SC 1000 KNX
communication object", after a long
press the pushbutton sensor starts with
the value transmitted by itself or by
another device with this group address
as the last value.
This parameter is only visible if "Value
adjustment by long button-press =
enabled"!
Direction of value
adjustment
Upwards
Downwards
Toggling (alternating)
With a long press, the push button
sensor can either vary the values always
in the same direction or it stores the
direction of the last adjustment and
reverses it on the next button-press.
This parameter is only visible if "Value
adjustment by long button-press =
enabled"!
Step width (1...15) 1...15 In a value adjustment, the pushbutton
sensor determines the new telegram
value from the previous value and the
preset step width. If the value falls below
the lower limit of the adjustment range
(0 or 0 %) or if it exceeds the upper limit
(255 or 100%), the sensor adapts the
step width of the last step automatically.
This parameter is only visible if "Value
adjustment by long button-press =
enabled"!
Time between two
telegrams
0.5 sec
1 sec
2 sec
3 sec
In a value adjustment, the pushbutton
sensor determines the new telegram
value from the previous value and the
preset step width. If the value falls below
the lower limit of the adjustment range
(0 or 0 %) or if it exceeds the upper limit
(255 or 100%), the sensor adapts the
step width of the last step automatically.
This parameter is only visible if "Value
adjustment by long button-press =
enabled"!
Value adjustment with
overflow ?
Yes
No
If value adjustment is to be effected
without overflow (setting "No") and if the
pushbutton sensor reaches the lower
limit of the adjustment range (0 or 0 %)
or the upper limit (255 or 100 %) during
value adjustment, the adjustment will be
stopped automatically by the sensor.
If the value adjustment with overflow is
programmed (setting "Yes") and if the
push button sensor reaches the lower or
the upper limit, it will transmit the value
of this range limit and then add a pause
the duration of which corresponds to two
levels. Thereafter, the push button
sensor transmits a telegram with the
value of the other range limit and
Page 318 of 347
Software "Smart Control 501511"
Parameters