Art. No. SC 1000 KNX
pushbutton sensor TSM is recalled or
stored again. In this case, the sensor
transmits no telegram to the bus via a
scene extension object. For this setting,
the internal scene function must be
enabled.
Scene number
(1...64)
Rocker 1.1
1...64 In accordance with the KNX standard,
objects with data type 18.001 "Scene
Control" can recall or store up to 64
scenes by their numbers. The parameter
defines the scene number to be
transmitted when the top (or left) of the
button is pressed.
Scene number
(1...64)
Rocker 1.2
1...64 In accordance with the KNX standard,
objects with data type 18.001 "Scene
Control" can recall or store up to 64
scenes by their numbers. The parameter
defines the scene number to be
transmitted when the bottom (or right) of
the button is pressed.
Scene number
(1...8)
Rocker 1.1
1...8 This parameter defines the number of
the internal scene which is recalled or
stored when the top (or left) of the
button is pressed.
Scene number
(1...8)
Rocker 1.2
1...8 This parameter defines the number of
the internal scene which is recalled or
stored when the bottom (or right) of the
button is pressed.
The following parameters are only visible for the rocker function "2-channel operation"...
Operation concept Channel 1 or channel 2
Channel 1 and channel 2
This parameter defines the 2-channel
operation concept. If the setting
"Channel 1 or channel 2" is selected, the
push button sensor decides dependent
on the button-press duration which of
the channels will be used.
If the setting "Channel 1 and channel 2"
is selected, the push button sensor
transmits only the telegram of channel 1
on a short button-press and both
telegrams on a sustained button-press.
Function channel 1 (2) No function
Switching (1 bit)
Value transmitter 0...255
(1 byte)
This parameter defines the channel
function and specifies which other
parameters and which communication
object are to be displayed for channel 1
(2).
Page 322 of 347
Software "Smart Control 501511"
Parameters

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Jung Smart Control SC 1000 KNX and is the answer not in the manual?

Jung Smart Control SC 1000 KNX Specifications

General IconGeneral
BrandJung
ModelSmart Control SC 1000 KNX
CategoryController
LanguageEnglish

Related product manuals