Art. No. SC 1000 KNX
Value adjustment by
long button-press
enabled
disabled
If value adjustment by long button-press
is enabled, the ETS shows further
parameters.
Value adjustment begins, when the
button is held down for more than 5 s. In
this case, the respective status LED
flashes as a sign that a new telegram
has been transmitted.
Starting value in case of
value adjustment
Same as configured value
Same as value after last
adjustment
Same as value from
communication object
Value adjustment can begin with
different starting values. This parameter
is only visible if "Value adjustment by
long button-press = enabled"!
In the setting "Same as parameterised
value", after each long press the
pushbutton sensor always starts with the
value programmed in the ETS.
In the setting "Same as value after last
adjustment", after a long press the
pushbutton sensor starts with the value
transmitted by itself or by another device
with this group address as the last
value.
In the setting "Same as value from
communication object", after a long
press the pushbutton sensor starts with
the value transmitted by itself or by
another device with this group address
as the last value. This setting is
selectable only if "Function = Value
transmitter (0...65535)"!
Direction of value
adjustment
Upwards
Downwards
Toggling (alternating)
With a long press, the push button
sensor can either vary the values always
in the same direction or it stores the
direction of the last adjustment and
reverses it on the next button-press.
Visible only if "Value adjustment by long
button-press = enabled"!
Step width 1 °C For temperature values, the step size of
the adjustment is fixed to 1°C. Visible
only if "Function = Temperature value
transmitter" and "Value adjustment by
long button-press = enabled"!
Step width 50 lux For brightness values, the step width of
the adjustment is fixed to 50 lux. Visible
only if "Function = Brightness value
transmitter" and "Value adjustment by
long button-press = enabled"!
Step width 1
2
5
10
This parameter sets the step width of
the value adjustment for the 2-byte
value transmitter. Only visible if
"Function = Value transmitter (0 ...
Page 330 of 347
Software "Smart Control 501511"
Parameters