Art. No. SC 1000 KNX
Function: Controller status
Object
h
90
Function
KNX status operating mode
Name
C.Output
Type
1 byte
DPT
20.102
Flag
C, -, T, (R)
1
Description 1-byte object used by the controller to output the operating mode in the event
of forced position.
Only when "Controller status" = "KNX compliant".
Objects for heating / cooling signal functions
Function: Heating energy message
Object
h
91
Function
Heating indication
Name
C.Output
Type
1-bit
DPT
1.001
Flag
C, -, T, (R)
1
Description 1-bit object for the controller to report a request for heating energy. Object
value = "1": energy request, object value = "0": no energy request.
Function: Cooling energy message
Object
h
92
Function
Cooling indication
Name
C.Output
Type
1-bit
DPT
1.001
Flag
C, -, T, (R)
1
Description 1-bit object for the controller to report a request for cooling energy. Object
value = "1": energy request, object value = "0": no energy request.
Objects for controller disabling functions
Function: Disable controller
Object
h
94
Function
Disable controller
Name
C.Input
Type
1-bit
DPT
1.001
Flag
C, W, -, (R)
2
Description 1-bit object for deactivating the controller (activating dew point operation).
Polarity: Controller deactivated = "1", controller activated = "0".
1: For reading, the R-flag must be set. The last value written to the object via the bus or by the
device will be read.
2: For reading, the R-flag must be set. The last value written to the object via the bus will be
read.