KaControl for Venkon
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
24
6.3.1 Terminal Resistors in a CAN Bus System
The bus lines between the CAN bus cards must be linear.
Disconnect the Venkons before adjusting the final resistors.
A terminating resistor must be connected to the first and last CAN
bus card in a bus line between terminals "+" and "-".
Resistance of terminating resistor: 120 Ohm
6.3.2 Bus connections between Venkons
Bus communication between Venkons and CAN bus cards is solely
via the CAN bus. The tLAN bus communication in single-circuit
controls between the Venkons is not connected.
• Refer to the technical datasheet on the CAN bus cards for the
connection conditions of the CAN bus cards.
Single circuit control
(maximum 30 units) communication
between the Venkons via CAN bus,
bus connection on the CAN bus card