KaControl for Venkon
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
43
10.3.7 Auto-Eco Function
There is an option to lock the fan stages depending on the water temperature using the clip-on
sensor. This application enables the central raising or lowering of the water temperatures in the
building and can be detected and managed on the respective Venkon.
When a clip-on sensor is used, DIP switch no. 1 must be set to ON (see Section 9 "Setting Unit
Configuration by Means of DIP Switches").
10.3.7.1 Limit Value of Water Temperature in Heating Mode
Parameter P10, P11, P12
Parameters P10, P11 and P12 can be used to set the limit values for switching on the fan stages in
Heating mode
10.3.7.2 Limit Value of Water Temperature in Cooling Mode
Parameter P14
Parameter P14 is used to set the limit value for switching on the fan stages in Cooling mode.
Operation Standard Min Max Unit
P10 Limit value to activate fan stage 1 in Heating mode 29 0 255 °C
P11 Limit value to activate fan stage 2 in Heating mode 33 0 255 °C
P12 Limit value to activate fan stage 3 in Heating mode 37 0 255 °C
Operation Standard Min Max Unit
P14 Limit value temperature to activate the fan stages in
Cooling mode
21 0 255 °C