KaControl for Venkon
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
31
8.2 Multi-circuit Controls
8.2.1 Maximum 10 Control Zones with up to 6 Venkons in
One Control Zone
KaControl Venkons in multi-circuit controllers must be addressed,
whereas only the master unit needs to be addressed in one
control circuit.
• Addressing is done by means of parameter settings in the Service
menu using the KaController.
• The master unit / slave unit in a control circuit is defined by the
connection of the control unit.
• By connecting a control unit to it, the respective Venkon
automatically becomes the master unit in the control circuit.
• A master unit need not necessarily be arranged at the end of a bus
system in a control circuit.
Addressing needed via parameter settings
RS485 card