11. Control PCB Parameter List
The parameters can be called up in the Service menu and adapted to meet the needs of the
system.
The steps to call up the Service menu are described in section 10.2.
Operation Standard Min Max Unit Note
P000 Software version (read-only) 0 255 -
P001 Basic target value for Setpoint input + 3K 22 8 32 °C Page 37
P002 Neutral zone - Cooling in Automatic mode 5 0 255 °C /10 Page 51
P003 Neutral zone - Heating in Automatic mode 5 0 255 °C /10 Page 51
P004 Switching on/off hysteresis - Cooling in Automatic
mode
10 0 255 °C /10 Page 51
P005 Switching on/off hysteresis - Heating in Automatic
mode
3 0 255 °C /10 Page 51
P006 Switching on/off hysteresis in manual fan mode 5 0 255 °C /10 Page 50
P007 Automatic fan mode: Stage 2 activation 7 0 255 °C /10 Page 59
P008 Automatic fan mode: Stage 3 activation 7 0 255 °C /10 Page 50
P009 Automatic fan mode: Switching on/off hysteresis
stages
5 0 255 °C /10 Page 50
P010 Clip-on sensor: Limit value temperature to activate
fan stage 1 in Heating mode
29 0 255 °C Page 40, 43
P011 Clip-on sensor: Limit value temperature to activate
fan stage 2 in Heating mode
33 0 255 °C Page 40, 43
P012 Clip-on sensor: Limit value temperature to activate
fan stage 3 in Heating mode
37 0 255 °C Page 40, 43
P013 Clip-on sensor: Hysteresis for limit value
temperatures P010, P011, P012, P014
10 0 255 °C/10
P014 Clip-on sensor: Limit value temperature to activate
fan stages in Cooling mode
21 0 255 °C Page 41, 43
P015 Operation of input B1 0 0 6 - Page 44
P016 Operation of input B2 0 0 6 - Page 44
P017 Operation of input B3 0 0 6 - Page 44
P018
Temperature increase of cooling setpoint in Eco
mode
30 0 255 °C /10 Page 39
P019 Temperature drop of heating setpoint in Eco
operating mode
30 0 255 °C /10 Page 39
P020 It is imperative that the standard value is set 6 0 15 -
P021 It is imperative that the standard value is set 6 0 15 -
P022 It is imperative that the standard value is set 0 0 1 -
P023 It is imperative that the standard value is set 0 -99 127 °C /10
P024 It is imperative that the standard value is set 0 -20 20 1/10
P025 It is imperative that the standard value is set 0 -99 127 °C /10
P026 It is imperative that the standard value is set 0 -20 20 1/10
P027 It is imperative that the standard value is set 0 0 2 -
P028 It is imperative that the standard value is set 0 1 3 -
P029 Activation of continuous fan mode 0 0 1 - Page 51
P030 It is imperative that the standard value is set 15 0 255 °C