10.3.8 Display of Heating Symbol / Cooling Symbol
Parameter P55
Parameter P55 can be switched on and off to display the heating and cooling system in Automatic
mode.
10.3.9 Function of Analogue Inputs B1, B2 and B3
The functions of the analogue inputs are specified by the DIP switch settings and cannot be changed
via the parameter settings.
The user has the option of calibrating the temperature sensor to the analogue inputs B1-B3 using
offset values. The temperature sensor should be calibrated during initial commissioning and at every
service.
10.3.9.1 Sensor Calibration
Parameter P58 − P65
Parameters P58 - P65 can be used to calibrate the sensor. The temperature sensor should be
calibrated during initial commissioning and at every service.
The temperature setpoint is shown as standard in the display. The measured temperature must be
displayed to calibrate the sensor.
Parameters P37=1 must be set so that the room temperature can be displayed (Room
temperature shown in the display, see Section 10.3.1).
KaControl for Venkon
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
44
Operation Standard Min Max Unit
P55 0 = Heating and cooling symbols are permanently
hidden
1 = Heating and cooling symbols are shown depending
on requirements
1 0 1
Operation Standard Min Max Unit
P58 Offset analog input B1 in Cooling mode 0 -99 127 °C /10
P59 Offset analog input B1 in Heating mode 0 -99 127 °C /10
P60 Offset analog input B1 in Automatic mode 0 -99 127 °C /10
P61 Offset sensor in the KaController 0 -99 127 °C /10
P62 Offset analog input B2 in Cooling mode 0 -99 127 °C /10
P63 Offset analog input B2 in Heating mode 0 -99 127 °C /10
P64 Offset analog input B3 in Cooling mode 0 -99 127 °C /10
P65 Offset analog input B3 in Heating mode 0 -99 127 °C /10