KaControl for Venkon
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
30
8. Addressing
8.1 Single-circuit Controls
8.1.1 Maximum 6 Venkons in One Control Zone
• Venkons in single-circuits with a maximum of 6 units need not be
addressed.
• The master unit / slave unit is defined by the connection of the
KaController.
• By connecting a KaController to it, the respective Venkon
automatically becomes the master unit in the control circuit.
• A master unit must not necessarily be arranged at the end of a bus
system.
• All BUS cables must be laid in a linear pattern. Star-shaped wiring
is not permitted.
.
8.1.2 Maximum 30 Venkons in One Control Zone
• Venkons in single-circuits with more than 6 units must be
addressed.
• They are addressed by means of DIP switch settings on the CAN
bus card.
• The master unit / slave unit is defined by the connection of the
KaController.
• By connecting a KaController to it, the respective Venkon
automatically becomes the master unit in the control circuit.
• Procedure for setting the address using DIP switch settings on the
CAN bus card:
1. Disconnect the Venkon
2. Remove CAN bus card from the basic PCB
3. Set the DIP switch as shown in the figure
4. Refit the CAN bus card to the basic PCB
5. Connect up the bus cable
6. Re-connect the Venkon
• The DIP switches on all CAN bus cards in a control circuit must be
set identically!
Addressing via DIP switches on
the CAN-Bus card
DIP switches on the rear of the
CAN-Bus card
DIP1 = ON
DIP2 = OFF
DIP3 = OFF
DIP4 = OFF
DIP5 = OFF
DIP6 = OFF
DIP7 = OFF
DIP8 = ON
DIP9 = OFF
DIP10 = OFF
Front view
Back view