10.3. Parameter Settings
10.3.1 Display of Setpoint Temperature/Room Temperature
Various values can be displayed using the large seven-segment display. The value is set using
parameter P37.
Parameter P37
10.3.2 Setting the Setpoint Temperature Absolute or ± 3K
Parameter P36
It may be necessary with office or hotel applications for the system
operator to specify a base setpoint. The user not only has the
option of changing the setpoint temperature by ± 3 K, to
compensate for a differing perception of the room temperature.
Alternatively the setpoint can be set in absolute values.
The setpoint setting can be configured via parameter P36.
The base setpoint for the "Setpoint setting + 3 K" can be configured
via parameter P01.
When setting the parameters
P37=0 → Display of setpoint temperature
P36=1 → Setpoint setting ± 3K
no setpoint value is shown in the standard view!
Parameter P36 = 0
"absolute" setting of setpoint
temperature
Parameter P36 = 1
Setting of setpoint
temperature ± 3K
Operation Standard Min Max Unit
P37
0 = Room temperature setpoint
1 = Current room temperature
2 = Temperature measurement B2
3 = Temperature measurement B3
0 0 3
KaControl for Venkon
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
37
Operation Standard Min Max Unit
P36 Setpoint setting
0 = Absolute setpoint setting
1 = Setpoint setting ± 3 K
0 0 1
Operation Standard Min Max Unit
P01 Base setpoint for setpoint
adjustment ± 3K
22 8 35 °C