KaControl for Venkon
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
32
8.2.2 Parameter Settings for Addressing Master Units
The following steps are needed to set the parameters:
1. Switch off the Venkon by:
• Pressing the ON/OFF key
or
• Pressing the navigator for a minimum of 5 seconds
or
• Turn the navigator to the left until OFF appears
2. Call up the Service menu by pressing the navigator for a minimum
of 10 seconds. The message "Para" and the "CODE" with the
value 000 is shown on the display in sequence.
3. Select the password (Code) 22 by turning the navigator and
confirm by pressing the navigator. You are now in Service level 1
and the display shows the current software version (P000=..).
4. Select parameter P92 (Access to Service level 2) by turning the
navigator and enter the value P92=66. You are now in Service
level 2. Enter the parameters in accordance with the table below
by turning the navigator.
5. Setting parameters:
• Select the parameter by turning the navigator.
• Call up Edit mode by pressing the navigator.
• Enter the required value by turning the navigator.
• Save the new value by pressing the navigator.
6. There are 3 ways to exit the Service menu and call up the
Standard view:
• If no action has been carried out using the navigator for 2
seconds
• Hold down the navigator for 5 seconds
• Press the navigator and select "ESC" in the display and confirm
by pressing the navigator
Parameter settings to address the control circuits
Parameter Name Setting range
P69 Number of control circuit 1–10
P54 RS485 0 communication 0