6.7 Outputs to Activate Ext. Control Units (e.g. heat
demand, faults etc.)
• All KaControl Venkon master units have multifunctional outputs
that can be assigned different functions (heat requirement,
cooling requirements, fault etc.)
• Connect up the cables in accordance with the wiring diagram and
configure the functions using the KaController.
• The maximum cable length between the master unit and the
external control units is 30 m.
6.8 Inlet Air Temperature Sensor
• All KaControl PCBs have analogue inputs to register the inlet air
temperature.
• There is no need to lay a separate cable to connect the inlet air
temperature sensor, as the connecting lines from the temperature
sensor can be connected directly to the PCB.
• Connect up the inlet air temperature sensor in accordance with
the wiring diagram and adjust the DIP switch in line with the
instructions in section 9.
• In control layout C2, an inlet air temperature sensor is integrated
as standard in the fan convector, while in layout C1 it must be
ordered separately.
Inlet air temperature sensor:
"all" fan convectors in a control zone must be fitted with an inlet
air temperature sensor.