KaControl for Venkon
ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
27
6.7 Outputs to Activate Ext. Control Units (e.g. heat
demand, faults etc.)
All KaControl Venkon master units have multifunctional outputs
that can be assigned different functions (heat requirement,
cooling requirements, fault etc.)
Connect up the cables in accordance with the wiring diagram and
configure the functions using the KaController.
The maximum cable length between the master unit and the
external control units is 30 m.
6.8 Inlet Air Temperature Sensor
All KaControl PCBs have analogue inputs to register the inlet air
temperature.
There is no need to lay a separate cable to connect the inlet air
temperature sensor, as the connecting lines from the temperature
sensor can be connected directly to the PCB.
Connect up the inlet air temperature sensor in accordance with
the wiring diagram and adjust the DIP switch in line with the
instructions in section 9.
In control layout C2, an inlet air temperature sensor is integrated
as standard in the fan convector, while in layout C1 it must be
ordered separately.
Inlet air temperature sensor:
"all" fan convectors in a control zone must be fitted with an inlet
air temperature sensor.