ASSEMBLY AND INSTALLATION INSTRUCTIONS
1.48
Venkon
55
Operation
Standard Min Max
Unit Note
P031 It is imperative that the standard value is set 20 0 255 °C
P032 Rinse function: Maximum idle time of fan 2 0 255 Min Page 42
P033 Rinse function: Duration of rinsing function 90 0 255 S Page 42
P034 Rinse function: Activation in operating modes
0 = Rinse function disabled
1 = Rinsing function enabled in: - Cooling mode
- Automatic mode
2 = Rinsing function enabled in: - Heating mode
- Automatic mode
3 = Rinsing function enabled in: - Cooling mode
- Heating mode
- Automatic mode
0 0 3 - Page 42
P035 It is imperative that the standard value is set 30 0 255 s
P036 Setpoint adjustment
0 = Absolute setpoint setting
1 = Setpoint adjustment + 3 K
0 0 1 - Page 37
P037 Display:
0 = Display of setpoint temperature
1 = Display of room temperature
2 = Display of sensor B2
2 = Display of sensor B3
0 0 4 - Page 37
P038 8 = Eco/Day mode changeover
26 = Eco/Day mode changeover + changeover
Heating/cooling via clip-on sensor (2-pipe
system)
72 = ON/OFF changeover
90 = ON/OFF changeover + Heating/Cooling
changeover via clip-on sensor (2-pipe system)
72 0 255 - Page 38, 40
P039 Digital output No4:
The function is defined as standard using the
DIP switch settings.
For non-standard valve PCBs see section 10.3.11.3
.. 0 18 - Page 46
P040 Digital output No5:
The function is defined as standard using the
DIP switch settings.
For non-standard valve PCBs see section 10.3.11.3
.. 0 18 - Page 46
P041 Digital Output No6:
0 = Output disabled
3 = Cooling requirement
4 = Heating requirement
7 = Unit malfunction
8 = Cooling requirement or heating requirement
3 0 18 - Page 46
P042 Digital Output No7:
0 = Output disabled
3 = Cooling requirement
4 = Heating requirement
7 = Unit malfunction
8 = Cooling requirement or heating requirement
4 0 18 - Page 47