Enter in LF.27 the pulses per revolution of the encoder, i.e. 1024, 2048,
4096 etc.
LF.28 can be used to swap the encoder channels such that the encoder
is incrementally counting in the same direction as the motor. Initially
leave this parameter set to 0 or no reversal. Whether or not reversal is
necessary will be determined later in section 5.11
LF.29 sets the sample time for the speed measurement. Initially the
default setting of 4 mSec will work  ne.
Set up of the encoder is complete!
The speed and torque controller are adjusted in parameters LF.30 through
LF.33, and LF.36. For initial start up the default settings will work. Once
the elevator is running at high speed, it might be necessary to come
back to adjust LF.31...LF.33. Parameters Ld.27 and Ld.28 are adjusted
automatically by the drive and should require no adjustment by the
user.
LF.30 is the one parameter which will need to be adjusted for initial
operation. If operating open loop set LF.30 = 0 and if operation is closed
loop speed or torque control initially set LF.30 = 2. Once the proper
direction of rotation is established LF.30 can be changed to a value of 4
if torque control is ultimately desired.
Set up of the controller is complete!
Initial Start Up
5.8.3 Other encoder
adjustments
5.9 Controller
Settings

Table of Contents

Other manuals for KEB COMBIVERT F5

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the KEB COMBIVERT F5 and is the answer not in the manual?

KEB COMBIVERT F5 Specifications

General IconGeneral
CategoryDC Drives
Enclosure RatingIP20
Control ModeVector Control, V/f Control
ProtectionOvercurrent, Overvoltage, Undervoltage, Overtemperature, Short circuit
Fieldbus CommunicationPROFIBUS, CANopen
Communication InterfacesRS-485
Input Voltage380-480V AC
Cooling MethodForced air cooling (fan)

Related product manuals