14. Relays
Volt free changeover relay contacts rated at 30 Volts DC at 1 Amp are provided for ancillary switching functions in all panels.
Under no circumstances should voltage or current outside of this limit be used with these contacts.
The default actions of these contacts as supplied from the factory are as described below: -
NAME ACTION
FIRE Activates on any fire condition and remains active until panel is reset
FAULT Activates on any fault or on total loss of power and clears when faults are cleared
ALARM Activates on any alarm, de-activates when alarm silenced / acknowledged
Each volt free changeover contact can be reconfigured independently for other actions via the PC configuration programme or the
front panel pushbuttons (at access level 3).
This includes delays as described for the sounder circuits above.