ZONE (0-500)
LOCATION TEXT (Up to 40 characters)
DAY SENSITIVITY
NIGHT SENSITIVITY
INDICATE PRE-ALARM
LOOP SOUNDER FITTED AS DETECTOR BASE
INPUT DELAY
OUTPUT DELAY BYPASS
For all other types of input however, there is an input action attribute, which empowers the system with control possibilities way
beyond that of a normal fire alarm. Care must be taken to ensure that the system complies to the requirements of EN54-2 and local
fire regulation requirements when these inputs are configured with delays or different input actions.
The following describes how the control panel will respond to each of these input actions.
18.2.1. Fire action
Being a fire control panel, the fire action will probably be the most widely used and a fire input will be announced by the following:
COMMON FIRE LEDS
ZONAL FIRE LEDs (If fitted)
PULSING BUZZER
PANEL SOUNDER OUTPUTS
ALARM CONTACT
FIRE CONTACT
LCD FIRE MESSAGE, ADDRESS AND LOCATION TEXT OF INPUT
18.2.2. Fault action
Inputs attributed the fault action will be announced by the control panel as follows:
GENERAL FAULT LED
CONTINUOUS BUZZER
FAULT CONTACT
LCD FAULT MESSAGE, ADDRESS AND LOCATION TEXT OF INPUT
18.2.3. Pre-alarm action
Sensors or inputs can generate a pre-alarm. The control panel will respond as follows to a pre-alarm:
PRE-ALARM LED
CONTINUOUS BUZZER
LCD PRE-ALARM MESSAGE, ADDRESS AND LOCATION TEXT OF INPUT
18.2.4. Tech. alarm action (Technical alarm)
To allow a message to appear at the panel without necessarily performing any actions, technical alarm input is available which
produces the following response by the panel:
CONTINUOUS BUZZER
LCD TECHNICAL ALARM MESSAGE, ADDRESS AND LOCATION TEXT OF INPUT
18.2.5. Evacuate action
The evacuate action allows all sounder outputs and sounders to be operated continuously from an input anywhere on the system
with the following response at the panel:
COMMON FIRE LED’s
CONTINUOUS BUZZER
ALARM CONTACT
PANEL SOUNDER OUTPUTS CONTINUOUS
LCD EVACUATE MESSAGE, ADDRESS AND LOCATION TEXT OF INPUT
18.2.6. Alert action
The alert action allows all sounder outputs and sounders to be operated in a pulsing mode from an input anywhere on the system
with the following response at the panel:
CONTINUOUS BUZZER
PANEL SOUNDER OUTPUTS PULSING
LCD FIRE ALERT MESSAGE, ADDRESS AND LOCATION TEXT OF INPUT
18.2.7. Security action
The security action allows appropriately configured Hochiki CHQ-BS sounders to sound the selected Security tone from an input
anywhere on the system with the following response at the panel:
LCD SECURITY ALERT MESSAGE, ADDRESS AND LOCATION TEXT OF INPUT
CONTINUOUS BUZZER
18.2.8. Silence alarm action
An input programmed as Silence will silence any sounders that are operating and display an event message on the panel for the
duration of the input being activated. The event is also stored in the event log.