No.5 VFD stop jogging.
No.5 VFD reset fault:
Read the operating frequency of No.5 VFD and the response operating frequency of the VFD is 50.00Hz:
Number of registers
or bytes
Rewrite the acceleration time 1(Function code A0.06) of No.5 VFD to 10.0s and can’t save after power
failure.
Read the output current of No.5 VFD and the response output current of the VFD is 30.0A.
Number of
registers or bytes
Read the deceleration time 1(Function code A0.07) of No.5 VFD and the response deceleration time of the
VFD is 6.0s.
Number of
registers or bytes
Scaling relationship of VFD:
A)Scaling of frequency C is 1:100.
If you want to make the VFD run at 50Hz,then the main reference should be set as 0x1388(5000).
B)Scaling of time is 1:10
If you want to set the acceleration time of the VFD as 30s,then the function code should be set as
0x012C(300).
C)Scaling of current is 1:10
If the response current of VFD is 0x012C (300), then current of the VFD is 30A.
D)Output power is the absolute value.
E)Other (such as the input and output terminals, etc.) please reference inverter user manual