111
111
No.5 VFD stop jogging.
Data frame
Address
Function code
Register address
Register content
Checksum
Request
0x05
0x06
0x3200
0x00C0
0x86A6
Response
0x05
0x06
0x3200
0x00C0
0x86A6
No.5 VFD reset fault:
Data frame
Address
Function code
Register address
Register content
Checksum
Request
0x05
0x06
0x3200
0x0280
0x8636
Response
0x05
0x06
0x3200
0x0280
0x8636
Read the operating frequency of No.5 VFD and the response operating frequency of the VFD is 50.00Hz:
Data frame
Address
Function
code
Register
address
Number of registers
or bytes
Register
content
Checksum
Request
0x05
0x03
0x3301
0x0001
None
0xDB0A
Response
0x05
0x03
None
0x02
0x1388
0x44D2
Rewrite the acceleration time 1(Function code A0.06) of No.5 VFD to 10.0s and can’t save after power
failure.
Data frame
Address
Function code
Register address
Register content
Checksum
Request
0x05
0x06
0x0006
0x0064
0x69A4
Response
0x05
0x06
0x0006
0x0064
0x69A4
Read the output current of No.5 VFD and the response output current of the VFD is 30.0A.
Data frame
Address
Function code
Register
address
Number of
registers or bytes
Register
content
Checksum
Request
0x05
0x03
0x3306
0x0001
None
0x6ACB
Response
0x05
0x03
None
0x02
0x012C
0x49C9
Read the deceleration time 1(Function code A0.07) of No.5 VFD and the response deceleration time of the
VFD is 6.0s.
Data frame
Function code
Register
address
Number of
registers or bytes
Register
content
Checksum
Request
0x03
0x0007
0x0001
None
0x344F
Response
0x03
None
0x02
0x003C
0x344F
Scaling relationship of VFD:
A)Scaling of frequency C is 1:100.
If you want to make the VFD run at 50Hz,then the main reference should be set as 0x1388(5000).
B)Scaling of time is 1:10
If you want to set the acceleration time of the VFD as 30s,then the function code should be set as
0x012C(300).
C)Scaling of current is 1:10
If the response current of VFD is 0x012C (300), then current of the VFD is 30A.
D)Output power is the absolute value.
E)Other (such as the input and output terminals, etc.) please reference inverter user manual