Fig.6-46 Sleep Function
6.17 Group C2
Simple PLC function
Simple PLC function is used to run different
frequency and direction in different time auto-
matically, as shown in Fig.6-46
Fig.6-46 Simple PLC function
In Fig.6-46, a1~a15 and d1~d15 are the
acceleration and deceleration of the steps. f1~f15
and T1~T15 are the setting frequency and
operating time of the steps. There parameters are
defined in group C2.
PLC step finish signal and PLC cycle finish signal
can be output with pulse signal which last 500ms by
bi-direction open collector output Y1, open collector
output Y or relay. Set function code as 12 and 13 for
parameters A6.14, A6.16 or A6.25.
The unit’s place of LED : PLC function running
mode
0: No function.
Simple PLC function is invalid.
1: Stop after single cycle.
As shown in Fig.6-47, the drive will stop
automatically after finishing one cycle running, the
wait for another start signal to startup.
Fig.6-47 Stop after single cycle
2. Keep final states after single cycle
As shown in Fig.6-48, the drive will keep running at
the frequency and direction in last step after
finishing single cycle.